Description
AC Input Capacity on Battery : 1000VA
AC Input Voltage : 100V or 110V/115V/120V or 220V/230V/240V
AC Input Frequency : 50 or 60 Hz +/-5% (auto sensing)
AC Input Range : +/- 25%
AC Input Surge Protection Outlet : 2
AC OUTPUT
AC Output Waveform : Simulated sine wave
AC Output Voltage : 115V+/- 5%
AC Output Frequency : 60 Hz +/- 0.5%
AC Output Voltage Regulation : AVR automatically increase output voltage 15% above input voltage if -9% to -25% of nominal. AVR drcrease output voltage 13% below input voltage if +9% to +25% of nominal
AC Output Transfer : 2/4 milliseconds, including detection time
PROTECTION
Protection Spike : 480 joules / 2 ms
Protection Overload : UPS automatic shutdown if overload exceeds 110% nominal at 60 seconds and 130% at 3 seconds
Protection Unit Fuse for overload & short circuit protection
Protection Inside Protectio : UPS output cut off immediately or input fuse protection
BATTERY
Battery Type : Sealed, maintenance-free lead acid bateries with 3-6 years typical lifetime
Battery Typical recharge 6 hours to 90% of full capacity
Battery Protection : Auto discharge protection
BACKUP TIME
Battery Backup Time Full Load : 8 minutes
Battery Backup Time Half Load : 17 minutes
PHYSICAL
Weight : 13.4Kg (29.5lbs)
Shipping Weight : 14.8Kg (32.6lbs)
Dimensions : 382x130x192mm (15.0×5.1×7.5″)
ALARM
Alarm Battery Backup slow beeping sound (about 0.47 Hz)
Alarm Battery Low Rapid beeping sound (about 1.82 Hz)
Alarm Overload : Continue beeping sound
INTERFACE
Interface RS-232 : YES
ENVIRONMENT
Environment Ambien :t 3,500 meters max. elevation, 0-95% humidity non-condensing, 0-40 deg C
Environment Audible : <40dBA (1 meter from surface) Environment Storage Condition 15,000 meters max. elevation